9 EN ● Make sure the protective earth ground wiring is correct. The current spec, color, position, connection and conductance reliability of wire sh
10 EN 3. Operations 3-1. Button Operation Button Function ON/Enter Button Turn on the UPS: Press and hold the button more than 0.5s to turn
11 EN LCD Panel: Display Function Backup time information Indicates the backup time in numbers. H: hours, M: minutes, S: seconds Fault infor
12 EN Battery information Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates the battery is fault. Indicates low ba
13 EN 3-4. Single UPS Operation 1. Turn on the UPS with utility power supply (in AC mode) 1) After power supply is connected correctly, set the
14 EN 3) Make sure the battery numbers setting on the control board (Please refer to the section 3-4-12 for detailed setting) is consistent to re
15 EN 10. Operation in warning status 1) When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems for
16 EN NCF Normal mode (not CVCF mode) CF CVCF mode SUB Subtract ADD Add ON On OFF Off FBD Not allowed OPN Allow RES Reserved 3-6. LCD Set
17 EN 19 Battery capacity and groups setting Y Y Y Y Y 20 Backup time calibration Y Y Y Y Y *Y means that this program can be set in this mode. 0
18 EN 04: Frequency range for bypass Interface Setting Parameter 2: Set the acceptable low frequency for bypass. 50 Hz system: Setting range i
1 EN Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefull
19 EN 09: Battery maximum discharge time setting Interface Setting Parameter 3: 000~999: Set the maximum discharge time from 0min to 999min. U
20 EN 14: Charger voltage adjustment Interface Setting Parameter 2: you may choose Add or Sub to adjust charger voltage Parameter 3: the voltage
21 EN 19: Battery capacity and groups setting Interface Setting Parameter 2: Set the battery capacity such as 7AH, 9AH, 10AH, 12AH, 17AH, 26
22 EN Battery mode Description When the input voltage is beyond the acceptable range or power failure, UPS will backup power from battery and alarm
23 EN 3-9. Warning Indicator Warning Icon (flashing) Alarm Battery low Beeping every second Overload Beeping twice every second Battery unconn
24 EN 4. Trouble Shooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause
25 EN 5. Storage and Maintenance 5-1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dr
26 EN 6. Specifications MODEL PowerWalker 6000 PowerWalker VFI 6000C/R LCD PowerWalker 10000 PowerWalker VFI 10000C/R LCD CAPACITY* 6000 VA / 4800 W
2 EN Table of Contents 1. SAFETY AND EMC INSTRUCTIONS ...
3 EN 1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using
4 EN 1-4. Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel th
5 EN 2. Installation and Operation There are two different types of online UPS: standard and long-run models. Please refer to the following model ta
6 EN Diagram 2: 6KL/10KL Rear Panel Diagram 3: 6K(L)/10K(L) Input/Output Terminal
7 EN 11. Grounding terminal 12. Utility input terminal 13. External maintenance bypass switch port 14. Battery pack output circuit breaker 2-3. Sing
8 EN NOTE 2: Please install the output breaker between the output terminal and the load, and the breaker should be qualified with leaka